The b2 electronics HVA68TD is a compact, portable VLF test set for assessing medium-voltage cables rated up to 46 kV, in accordance with IEEE 400.2. Besides VLF testing with sine and square wave and DC testing, it performs sheath testing and sheath fault location (an additional sheath fault locator is needed). Its Tan Delta diagnostics unit is built in, so one unit handles both the withstand test and the condition assessment of the cable insulation.
With its high output power it can test cables up to 7 km long at 48 kVrms and 0.1 Hz (250 pF/m, 1.7 µF load), or several phases in parallel. It also runs the Monitored Withstand Test (MWT) per IEEE 400.2, which combines withstand testing with Tan Delta measurement. If the cable breaks down during a VLF test, the Arc Pre-Location (APL) function gives the distance to the failure, which shortens the fault location work that follows. Results are stored on the unit and downloaded via USB or Bluetooth for reporting with b2 ControlCenter (included), so no laptop is needed on site.
Max 68 kVpeak / 48 kVrms output
For MV cables rated up to 46 kV (IEEE 400.2)
Integrated Tan Delta diagnostics and Monitored Withstand Test (MWT)
Arc Pre-Location (APL): distance to the failure point after a breakdown
VLF sine and square wave, DC, sheath test and vacuum bottle test
Load-independent pure sinusoidal output over the entire power range
Continuous operation, no thermal limitation
Dual electronic and mechanical discharge, 12 kV backfeed protection
Expandable with b2 PD or PDTD diagnostics, such as the PDTD68
Output voltage | VLF sine 0–68 kVpeak / 0–48 kVrms; DC −68 to +68 kV; VLF square 0–68 kV; sheath test 0–15 kV (negative) |
|---|---|
Frequency | 0.01–0.1 Hz |
Output load | 1.7 µF @ 0.1 Hz @ 48 kVrms |
Test capability | Cables up to 7 km (250 pF/m) at 48 kVrms, 0.1 Hz |
Output current | AC 56 mArms max., DC 100 mA max. |
Tan Delta | Accuracy ±0.1 E-3 (10 nF–10 µF); resolution 0.01 E-3 (mean) |
Arc Pre-Location | 80 m to 10 km, 0.1 m resolution |
Test types | VLF withstand, VLF Tan Delta, MWT, DC, sheath test, sheath fault location, vacuum bottle test |
Compliance | IEEE 400.2; DIN VDE 0276-620 / -621 (CENELEC HD 620 S2, HD 621 S1); IEC 60502-2 / IEC 60229 |
Safety | Dual Discharge Device, 12 kV backfeed protection (50/60 Hz), external interlock, key switch |
Data | 50 reports and 50 test sequences in memory, USB, Bluetooth, b2 ControlCenter included |
Power supply | 190–240 V, 50/60 Hz, 3,000 VA (120 V operation: 1,500 VA) |
Operating temperature | −10 to +55 °C |
Dimensions / weight | 593 × 340 × 513 mm / 63 kg |
What does the HVA68TD add over a standard VLF test set?
The Tan Delta diagnostics unit is built in, so the same set runs the withstand test, Tan Delta measurement and the Monitored Withstand Test per IEEE 400.2. It also gives the distance to the failure if the cable breaks down during the test (Arc Pre-Location).
Can it measure partial discharge?
Partial discharge needs a PD unit. The HVA68TD can be extended at any time with b2 PD or PDTD products. b2 suggests the PDTD68, which measures PD and Tan Delta together up to 68 kV.
Where can I buy the b2 HVA68TD in Saudi Arabia?
From Mushor Technology, an authorized b2 electronics distributor in Saudi Arabia. Contact us by phone, WhatsApp or email for a quotation.
Which b2 models are similar to the HVA68TD, and how do I choose?
Choose by the voltage rating of the cables you test (per IEEE 400.2) and the cable length, which sets the capacitive load the set must drive. Models with TD in the name add integrated Tan Delta diagnostics. Similar b2 VLF test sets:
Mushor Technology is an authorized b2 electronics distributor in Saudi Arabia. We supply the b2 electronics HVA68TD VLF test set, along with the b2 PDTD68 and other b2 PD and Tan Delta diagnostics. Contact us for a quotation.
Related products
More in this category
Customer reviews
No reviews yet.