The b2 electronics HVA54-3 is a member of the HVA series with extra power, with an output current up to 120 mA, which greatly extends the maximum load and the testable cable length. It assesses the condition of medium-voltage cables up to 30 kV in accordance with IEEE 400.2, and besides VLF testing with sine and square wave and DC testing it performs sheath testing and sheath fault location (an additional sheath fault locator is needed).
It can test cables up to 11 km long at 38 kVrms and 0.1 Hz (250 pF/m, 2.7 µF load). The output stays purely sinusoidal over the entire power range, operating time has no thermal limit, and the dry system with non-arcing contacts needs no oil changes. Results are stored on the unit and downloaded via USB for reporting with b2 ControlCenter, so no laptop is needed on site.
Max 54 kVpeak / 38 kVrms output
For MV cables up to 30 kV (IEEE 400.2)
Extra power: output current up to 120 mA DC
VLF sine and square wave, DC, sheath and vacuum bottle tests
Load-independent pure sinusoidal output
Continuous operation, no thermal limitation
Electronic and mechanical discharge, 12 kV backfeed protection
Breakdown and load detection, real-time oscilloscope display
Dry system, no oil changes
Expandable with b2 PD, TD or PDTD diagnostics such as the PDTD68
Output voltage | VLF sine 0–54 kVpeak / 0–38 kVrms; DC −54 to +54 kV; VLF square 0–54 kV; sheath test 0–10 kV (negative) |
|---|---|
Frequency | 0.01–0.1 Hz, setting resolution 0.01 Hz |
Output load | 2.7 µF @ 0.1 Hz @ 38 kVrms |
Test capability | Cables up to 11 km (250 pF/m) at 38 kVrms, 0.1 Hz |
Output current | AC 85 mArms max., DC 120 mA max.; sheath test trip 0.1–5 mA; sheath fault location 35 mA max. |
Test types | VLF withstand, DC, sheath test, sheath fault location, vacuum bottle test |
Compliance | IEEE 400.2; DIN VDE 0276-620 (CENELEC HD 620 S2), DIN VDE 0276-621 (CENELEC HD 621 S1); IEC 60502-2 / IEC 60229 |
Safety | Dual Discharge Device, 12 kV backfeed protection (50/60 Hz), external interlock, key switch |
Data | USB, RS232; memory for 50 reports and 40 test sequences; b2 ControlCenter and HVA ControlCenter included |
Power supply | 190–240 V, 50/60 Hz, 3,000 VA |
Operating temperature | −10 to +50 °C |
Dimensions / weight | 450 × 340 × 520 mm / 57 kg |
Suggested diagnostics | b2 PDTD68 (PD & TD), b2 TD60-MC (Tan Delta) |
Which cables can the HVA54-3 test?
Medium-voltage cables up to 30 kV according to IEEE 400.2, with cables up to 11 km long at 38 kVrms and 0.1 Hz.
Can it be used for cable diagnostics?
Yes. It can be extended to a full diagnostics system with b2 PD, TD or PDTD products. b2 suggests the PDTD68 and the TD60-MC for this set.
Where can I buy the b2 HVA54-3 in Saudi Arabia?
From Mushor Technology, an authorized b2 electronics distributor in Saudi Arabia. Contact us by phone, WhatsApp or email for a quotation.
Which b2 models are similar to the HVA54-3, and how do I choose?
Choose by the voltage rating of the cables you test (per IEEE 400.2) and the cable length, which sets the capacitive load the set must drive. Models with TD in the name add integrated Tan Delta diagnostics. Similar b2 VLF test sets:
Mushor Technology is an authorized b2 electronics distributor in Saudi Arabia. We supply the b2 electronics HVA54-3 VLF test set, along with b2 PD and Tan Delta diagnostics such as the PDTD68. Contact us for a quotation.
Related products
More in this category
Customer reviews