The b2 electronics HVA28TD is a compact, portable VLF test set for assessing the condition of medium-voltage cables up to 15 kV, in accordance with IEEE 400.2. Besides VLF testing with sine and square wave and DC testing, it performs sheath testing and sheath fault location (an additional sheath fault locator is needed). Its integrated Tan Delta diagnostics unit measures with an accuracy of ±0.1 × 10⁻³ and enables the Monitored Withstand Test (MWT) per IEEE 400.2.
It can test cables more than 2 km long at 21 kVrms and 0.1 Hz (250 pF/m, 0.5 µF load), and its duty cycle is continuous with no thermal limitation. The rugged case is rated IP67 with the lid closed, so no extra transport box is needed. Results are stored on the unit and downloaded via USB or Bluetooth for reporting with b2 ControlCenter (included) or b2 Suite, so no laptop is needed on site.
Max 29 kVpeak / 21 kVrms output
For MV cables up to 15 kV (IEEE 400.2)
Integrated Tan Delta, accuracy ±0.1 × 10⁻³
Monitored Withstand Test (MWT) per IEEE 400.2
VLF sine and square wave, DC, sheath and vacuum bottle tests
Load-independent pure sinusoidal output
Continuous operation, no thermal limitation
Electronic and mechanical discharge, 12 kV backfeed protection
IP67 with the lid closed
USB and Bluetooth, b2 ControlCenter included
Expandable with b2 PD, TD or PDTD diagnostics such as the PDTD68
Output voltage | VLF sine 0–29 kVpeak / 0–21 kVrms; DC −28 to +28 kV; VLF square 0–28 kV; sheath test 0–15 kV (negative) |
|---|---|
Frequency | 0.01–0.1 Hz, setting resolution 0.01 Hz |
Output load | 0.5 µF @ 0.1 Hz @ 21 kVrms |
Test capability | Cables more than 2 km (250 pF/m) at 21 kVrms, 0.1 Hz |
Output current | AC 12 mArms max., DC 17 mA max.; sheath test trip 0.1–10 mA; sheath fault location 17 mA max. |
Test types | VLF withstand, DC, sheath test, sheath fault location, vacuum bottle test, VLF Tan Delta, Monitored Withstand Test |
Tan Delta | Range 0.1–999 E-3, accuracy ±0.1 E-3 |
Compliance | IEEE 400.2; DIN VDE 0276-620 (CENELEC HD 620 S2), DIN VDE 0276-621 (CENELEC HD 621 S1); IEC 60502-2 / IEC 60229 |
Safety | Dual Discharge Device, 12 kV backfeed protection (50/60 Hz), external interlock, key switch |
Data | USB, Bluetooth; memory for 50 reports and 50 test sequences; b2 ControlCenter included |
Power supply | 100–240 V, 50/60 Hz, 400 VA |
Operating temperature | −20 to +55 °C, IP67 (lid closed) |
Dimensions / weight | 417 × 221 × 334 mm / 14 kg |
Suggested diagnostics | b2 PDTD68 (PD & TD), b2 TD60-MC (Tan Delta) |
Which cables can the HVA28TD test?
Medium-voltage cables up to 15 kV according to IEEE 400.2, with cables more than 2 km long at 21 kVrms and 0.1 Hz.
What does the integrated Tan Delta add?
It measures the dielectric condition of the cable insulation during testing, with an accuracy of ±0.1 × 10⁻³, and enables the Monitored Withstand Test (MWT) per IEEE 400.2, which combines withstand testing with Tan Delta measurement.
Where can I buy the b2 HVA28TD in Saudi Arabia?
From Mushor Technology, an authorized b2 electronics distributor in Saudi Arabia. Contact us by phone, WhatsApp or email for a quotation.
Which b2 models are similar to the HVA28TD, and how do I choose?
Choose by the voltage rating of the cables you test (per IEEE 400.2) and the cable length, which sets the capacitive load the set must drive. Models with TD in the name add integrated Tan Delta diagnostics. Similar b2 VLF test sets:
Mushor Technology is an authorized b2 electronics distributor in Saudi Arabia. We supply the b2 electronics HVA28TD VLF test set, along with b2 PD and Tan Delta diagnostics such as the PDTD68. Contact us for a quotation.