b2 PD60-2 Partial Discharge Diagnostics System

The b2 electronics PD60-2 is a portable VLF diagnostics system for medium-voltage cables, designed for use with b2 HVA VLF test sets. It has an integrated partial discharge (PD) unit and can be extended later with a Tan Delta (TD) unit. Together with the HVA60 it forms a complete cable test and diagnostics system up to 62 kVpeak / 44 kVrms. According to b2, it suits XLPE, PE, EPR and PILC cables up to 100 km long, as well as rotating machines and transformers.

PD faults are located in real time with 1% accuracy and a resolution of 0.1 pC and 0.1 m, with a PD background level below 10 pC. Cables of different lengths are measured at constant frequency, so results can be compared with earlier measurements across the grid. The b2 Suite software guides the whole process with automated PD algorithms, test standard sequences with limits, phase-resolved PD display and a searchable database for comparing past measurements.

Related products

b2 electronics GmbH

b2 PD30-E Partial Discharge Diagnostics System

Model: PD30-E
b2 electronics GmbH

b2 PD90-2 Partial Discharge Diagnostics System

Model: PD90-2
b2 electronics GmbH

b2 HVA60 VLF High Voltage Test Set

Model: HVA60

More in this category

b2 electronics GmbH

b2 CTL12 Cable Sheath Tester and Fault Locator

Model: CTL12
b2 electronics GmbH

b2 HVA120 VLF High Voltage Test Set

Model: HVA120
b2 electronics GmbH

b2 HVA28 VLF High Voltage Test Set

Model: HVA28

Customer reviews

No reviews yet.