The b2 electronics PD120-2 is a portable VLF diagnostics system for medium-voltage cables, designed for use with b2 HVA VLF test sets. It has an integrated partial discharge (PD) unit and can be extended later with a Tan Delta (TD) unit. Together with the HVA120 it forms a complete cable test and diagnostics system up to 120 kVpeak / 85 kVrms. According to b2, it suits XLPE, PE, EPR and PILC cables up to 100 km long, as well as rotating machines and transformers.
PD faults are located in real time with 1% accuracy and a resolution of 0.1 pC and 0.1 m, with a PD background level below 10 pC. Cables of different lengths are measured at constant frequency, so results can be compared with earlier measurements across the grid. The b2 Suite software guides the whole process with automated PD algorithms, test standard sequences with limits, phase-resolved PD display and a searchable database for comparing past measurements.
Operating voltage up to 120 kVpeak / 85 kVrms (sine wave)
Integrated PD unit, extendable with Tan Delta
For MV cables up to 100 km (XLPE, PE, EPR, PILC)
PD localization with 1% accuracy, 0.1 pC and 0.1 m resolution
PD background level below 10 pC
PD measuring range 0.1 pC to 100 nC, 100 MHz bandwidth
Setup and calibration per IEC 60270
Phase-resolved PD display and comprehensive reporting
Built-in battery for the PD unit, mains operation 110–240 V
Works with b2 HVA VLF test sets such as the HVA120
Operating voltage | 1–120 kVpeak / 1–85 kVrms, sine wave |
|---|---|
Operating frequency | 0.01–0.1 Hz in 0.01 Hz steps (default 0.1 Hz) |
Test types | Partial discharge |
Coupling capacitor / HV filter | ~1 nF / ~1 nF |
PD measuring range | 0.1 pC to 100 nC, background level < 10 pC |
PD localization | 0.1 m to 100 km, 1% of cable length, resolution 0.1 pC and 0.1 m |
Propagation velocity (v/2) | 10–150 m/µs |
Sample rate / bandwidth | Up to 250 MS/s / 100 MHz |
Signal amplification | 0–52 dB (channel 1), 0–72 dB (channel 2) |
Compliance | IEEE 400.2 and 400.3, HD 620, CEI EN 50393, IEC 60270, IEC 60502-2 |
Power | 110–240 V, 50/60 Hz, max. 240 VA; PD built-in battery 6 V, 42 Wh (about 4 h at full load) |
Data / software | USB type B; b2 Suite v1.8 included, b2 Suite v2 optional |
Operating temperature | −5 to +45 °C |
Coupling capacitor | 330 × 280 × 870 mm, 24.7 kg |
HV filter | 300 × 280 × 720 mm, 34.0 kg |
In the box | Coupling capacitor, HV filter, PDC1 calibrator 10 pC–10 nC, HV test leads, grounding cables, PD impedance, fiber-optic USB converter, b2 Suite v1.8 licences, wheeled transport cases |
Can Tan Delta be added to the PD120-2 later?
Yes. The PD120-2 has an integrated PD unit and can be extended with the Tan Delta unit. The PDTD120-2 version ships with both.
Which VLF test set does the PD120-2 work with?
It is designed for b2 HVA VLF test sets. b2 pairs it with the HVA120 for a complete system up to 120 kVpeak.
Where can I buy the b2 PD120-2 in Saudi Arabia?
From Mushor Technology, an authorized b2 electronics distributor in Saudi Arabia. Contact us by phone, WhatsApp or email for a quotation.
Which b2 diagnostics systems are similar to the PD120-2, and how do I choose?
Choose by the test voltage you need, which should match your b2 HVA VLF test set, and by the method: PD for partial discharge, TD for Tan Delta, or PDTD for both. Similar b2 diagnostics systems:
Mushor Technology is an authorized b2 electronics distributor in Saudi Arabia. We supply the b2 electronics PD120-2, along with b2 HVA VLF test sets and other b2 PD and Tan Delta diagnostics. Contact us for a quotation.
Related products
More in this category
Customer reviews
No reviews yet.